At a recent industry meeting it was agreed that there is a need for some guidance related to the implementation of the latest edition of API/IP 1581.

This Bulletin is valid with immediate effect but the following key dates should be noted:
a) New filter separator vessel purchases shall be specified for 5th edition compliance with immediate effect (see item (1) on page 2 for guidance).
b) Installed 3rd edition coalescer elements can continue in service until replacement is required, due to maximum differential pressure or 3 years, but subject to a final change-out date of June 30, 2008.
c) Purchased stocks of 3rd edition coalescer elements can be used for replacement purposes until June 30, 2006, but subject to a final change-out date of June 30, 2008.

At Joint Venture airport locations, any variation of the above dates requires the approval of the international head offices of the participant companies.

DOWNLOAD THE BULLETIN

JIG Bulletin No. 7 (Oct 2005) – Filter Separators API/IP 1581 5th Edition